Ballast
lumen factors for control gear incorporating Perferm™ technology
(suitable
for all lamps including low Mercury & Amalgam lamps)
Module Number
Lamp T8/T12
Lamp
T5
T5 Circular
Lamp
2D
Lamp
TC-L
Lamp
TC-S/E
Lamp TC-D/E
Lamp TC-T/E Amalgam
No
of cells
l
18W18W
18W18W
18W18W
18W18W
18W
20W
30W
36W
40W
58W
70W
100W
8W
14W
21W
24W
28W
35W
39W
49W
54W
80W
22W
40W
55W
16W
21W
28W
38W
55W
18W
24W
34W
36W
40W
55W
5W
7W
9W
11W
10W
13W
18W
26W
13W
18W
26W
32W
42W
57W
PH4003P3
PL4003P3
PLR5003P3
18W18W
3 x 4Ah
12
12
9
9
9
24
16
13
12
13
20
22
23
20
20
29
12
PH4005P3
PL4005P3
PLR5005P3
4 x 4Ah
11
11
10
10
10
20
11
11
18
13
12
12
25
26
24
26
29
17
16
MT5414P3
4 x 4Ah
32
PH4007P3
PL4007P3
PLR5007P3
4 x 4Ah
10
11
9
9
11
13
12
PH4403P3
PL4403P3
PLR5403P3
4 x 4Ah
23
16
PH4418P3
PL4418P3
PLR5418P3
4 x 4Ah
25
25
42
32
40
37
38
40
PH4009P3
PL4009P3
PLR5009P3
5 x 4Ah
13
13
13
11
24
29
14
15
14
11
33
PH4506P3
PL4506P3
PLR5506P3
5 x 4Ah
28
25
26
30
28
25
22
23
22
20
PH4011P3
PL4011P3
PLR5011P3
5 x 4Ah
10
7
11
9
10
11
MT5528P3
5 x 4Ah
28
25
26
PHR5607P3
6 x 4Ah
18
18
18
16
13
14
20
PHR5608P3
6 x 4Ah
11
10
12
12
PHR5809P3
8 x 4Ah
15
14
9
27
24
20
17
30
15
18
MT5854P3
8 x 4Ah
27
24
20
17
PHR5108P3
10 x 4Ah
17
10
10
11
13
MT5108P3
10 x 4Ah
10
Ballast lumen factors for
emergency control gear (not suitable for low Mercury and Amalgam
lamps)
Module Number
Lamp T8/T12
Lamp
T5
T5
Circular
Lamp 2D
Lamp
TC-L
Lamp
TC-S/E
Lamp
TC-D/E
Lamp
TC-T/E Amalgam
No
of cells
M2019/3(NM)
MS2020/3(M3)
18W18W
2
x 4Ah
26
M2001P3(NM)
3
x 4Ah
24
34
MS2001P3
MH4001P3
ML4001P3
3 x 4Ah
24
24
34
25
22
28
20
23
33
MS2003P3
MH4003P3
ML4003P3
3 x 4Ah
14
14
14
17
MS2007P3
MH4007P3
ML4007P3
4 x 4Ah
12
10
29
21
14
13
13
MS2011P3
MH4011P3
ML4011P3
5 x 4Ah
13
13
10
9
14
21
14
13
13
18
Perferm™ technology is an ongoing development
involving the latest lamp technology and as such is subject to change as
and when further lamps/data become available.
We
strongly recommend that modules incorporating Perferm™ technology are used in all emergency
luminaires and conversions to provide the ultimate future proofing against
lamp evolution.
Most modules and
PCB's are tested and approved to EN60924/EN60925. They are EMC compliant
to EN55015 and carry the British Standard Kitemark and CE
mark.
They incorporate over
temperature and charger short circuit protection.
Mains supply 230V -
6% + 10% 50/60Hz power consumption 8VA (other supply Voltages available on
request).
Output circuitry uses
a high efficiency sinusodial inverter, with nominal operating current of 1
Amp.
Available as standard
in 3 hour operation (other durations to order).
All modules have
battery over discharge protection as standard (DDP) to prevent discharge
below 1 Volt per cell.
Reverse battery
polarity protected.
All connections are
via terminal blocks with a green light emitting diode (LED), to indicate
correct charging conditions. All products are supplied with LED
indicators.
Operating temperature
range module 0 to 70°C (centre side of case)
Printed circuit
boards 0 to 90°C (coil/core of charging transformer)
All ballast lumen
factors are shown as worst case.
All products listed
above are for 3 hours duration
All figures are based